== Automatic SFT constraint generation in EMO ==
+
== SFT constraints in SPD ==
 
The aim of automatic SFT constraint modelling in EMO is to model the SFT constraints that are generated as part of the dispatch and pricing solution in SPD.  These constraints are designed to avoid thermal overloading of a line in the event of the unexpected outage of any other line.
 
The aim of automatic SFT constraint modelling in EMO is to model the SFT constraints that are generated as part of the dispatch and pricing solution in SPD.  These constraints are designed to avoid thermal overloading of a line in the event of the unexpected outage of any other line.
SFT constraints appear in the dispatch and pricing optimisation model as linear constraints between two lines.  For example:
+
SFT constraints appear in the dispatch and pricing optimisation model as linear constraints involving two lines.  For example:
   -0.902*OHK_WRK.1+1.274*THI_WKM1.1 <= 605.79
+
   -0.902 &times; OHK_WRK.1+1.274 &times; THI_WKM1.1 &le; 605.79
In this case THI_WKM1.1 is the line being protected from overload and OHK_WRK.1 is the line which may cause overload in THI_WKM1.1 if it has an outage.  The general form of the SFT constraint is  
+
In this case THI_WKM1.1 is the line being protected from overload and OHK_WRK.1 is the line which may cause overload in THI_WKM1.1 if it has an outage (the contingent line).  The general form of the SFT constraint is  
  Equation 1.  <math>A F_{M} + B F_{C} \leq C</math>
+
{|
Where <math>F_{M}</math> is the flow on the protected line and  <math>F_{C}</math> is the flow on the contingent line.
+
|style="width: 100px"|'''Equation 1.'''  
The physical nature of the SFT constraint depends on various characteristics of the line being protected, the thermal environment and the mitigating measures available if an outage occurs.  The constraint can be expressed as a function of the loading on the line before an outage occurs (pre-contingent) and the loading after an outage occurs (post-contingent).  The higher the line is loaded pre-contingency the greater its expected temperature, giving it less capacity to absorb extra power in the event of a contingency
+
|\[ A F_{m} + B F_{c} \leq C \]
 +
|}
  
The physical SFT constraint is shown in the diagram 1.  This constraint will depend on the thermal environment
+
Where \(F_{m}\) is the flow on the ''protected line'' and  \(F_{c}\) is the flow on the ''contingent line''.
   Diagram 1.  Physical SFT constraint on a single line[[File:Diagram1.PNG]]
+
The physical nature of the SFT constraint depends on various characteristics of the line being protected, the thermal environment and the mitigating measures available if an outage occurs.  The constraint can be expressed as a function of the loading on the line before an outage occurs (pre-contingent) and the loading after an outage occurs (post-contingent).  The higher the line is loaded pre-contingency the greater its expected temperature, giving it less capacity to absorb extra power in the event of a contingency.
 +
 
 +
The physical constraint on the protected line that is modelled with SFT is shown in the diagram 1.  This constraint will depend on the thermal environment
 +
   [[File:Diagram_SFT_1.PNG|500px|thumb|none|Diagram 1.  Physical SFT constraint on a single line]]
  
 
In SPD the constraint above is modelled as a linear constraint which represents a tangent of the physical constraint at the point where the pre-contingent power flow matches the power flow in the solution of SPD.  Because the constraint may affect dispatch this is an iterative process, the resulting constraint is shown in diagram 2.
 
In SPD the constraint above is modelled as a linear constraint which represents a tangent of the physical constraint at the point where the pre-contingent power flow matches the power flow in the solution of SPD.  Because the constraint may affect dispatch this is an iterative process, the resulting constraint is shown in diagram 2.
   Diagram 2.  Physical SFT constraint on a single line[[File:Diagram2.PNG]]
+
   [[File:Diagram_SFT_2.PNG|500px|thumb|none|Diagram 2.  Physical SFT constraint on a single line]]
The power flows used in this relationship are from and AC power flow model, which will be constructed using the SPD solution in conjunction with reactive power modelling and a detailed model of the transmission grid componentry. The full information for creating this AC model is not available to us, so there is inevitable degree of approximation in estimating SFT constraints from our point of view.
+
 
To model this constraint in EMO we also need to estimate the nature of the pre/post power flow constraint as much as it relates to the SPD solution. We do not currently have access to the definitions of these functions, but we are informed that they are quadratic functions and they will pass through the point (C, C) where C is the thermal capacity of the line, which is a value we do have access to.  
+
== Estimating the constraint curves used by SPD ==
The slope of the curve is given explicitly in the resulting constraint equation in SPD, being negative the value A in Equation 1. We also have the arc flows from the SPD solution, so given enough instances of an SFT equation for a particular protected line we might be able to its pre/post constraint curve. We are informed that the thermal environment used for each curve is purely dependent on the Summer/Shoulder/Winter designation of the trading period so we can make a sample of all the constraints that fall into each category.
+
 
  To estimate the curve then we can try to find the linear relationship between the slope and the pre-contingent flow. What we are looking for in the equations we are seeing in SPD is two values, call them α, β, for which the following relationships exist over all instances of a particular combination of SFT constraint and thermal environment
+
Up to version 5.2.13 estimates of the constraint curves were based on observing historical constraints (see [[EMO:Estimation From Historical Constraints|Estimation From Historical Constraints]])
 +
 
 +
However from version 5.2.13 onwards the thermal characteristics of the circuit are used to calculate the thermal constraint curve.  This ensures that previously unconstrained lines may be modeled as effectively as possible.  It also requires the conductor type and configuration is entered into the model for each modeled line. The methods used to define and use the circuit's thermal characteristics are described in [[EMO:Use of line conductor information in SFT]]
 +
 
 +
== SFT constraint modelling in EMO ==
 +
[[File:ScreenShot SFT.PNG|1022px|thumb|none|Diagram 1.  SFT Protection factor trait in EMO]]
 +
 
 +
Among the traits shown for a circuit in EMO is the SFT protection factor, SFT protection factor curvature and SFT threshold (shown here under the columns "'''SFT PF'''", "'''SFT PFQ'''", "'''SFT Threshold'''" respectively).  The SFT protection factor and curvature will determine the nature of the SFT constraints generated by EMO.  The SFT protection factor is one minus the estimated slope of the thermal constraint curve at the point it passes through the point of maximum thermal capacity. For example if the slope at that point is such that 0.05 MW extra capacity is available for every 1 MW the flow is below the maximum thermal capacity then the SFT protection factor will be 1.05. Setting the SFT protection factor to a high number will tend to relax any constraints on that line. The SFT protection factor curvature is the rate at which this slope changes as the the powerflow is reduced (per 100MW).  These two factors together with the maximum thermal capacity define a quadratic curve that we will call the 'estimated thermal constraint curve', this should be a close approximation of the physical SFT constraint in Diagram 1.
 +
 
 +
When making a dispatch with Auto-SFT on EMO will search for lines that may be overloaded by an outage in another line. The effect of an outage at the contingent line (C) on the power flow on the protected line (M) can be estimated as a proportion of the flow on C being transferred to M.
 +
 
 +
{|
 +
|style="width: 100px"|'''Equation 4.'''  
 +
|\[F'_{m} = F_{m} + B{F}_{m}\]
 +
|}
 +
 +
Where \(F'_{m}\) is the post-contingent flow on the protected line.
 +
To ensure the point \(( F_{m}\), \(F'_{m})\) does not lie outside the estimated thermal constraint curve, a linear constraint is added to the dispatch model as follows
 +
 
 +
{|
 +
|style="width: 100px"|'''Equation 5.''' 
 +
|\[AF_{m} + BF_{c} \leq A \underline{C}\]
 +
|}
 +
 
 +
Where A is equal to the slope of the tangent line to the estimated thermal constraint curve and C is the y-intersect of this line. Once the exposed lines are identified and the related constraints are added to the model the dispatch is reiterated.  Eventually all relevant SFT constraints should be found and applied.

Latest revision as of 09:02, 21 December 2015

SFT constraints in SPD

The aim of automatic SFT constraint modelling in EMO is to model the SFT constraints that are generated as part of the dispatch and pricing solution in SPD. These constraints are designed to avoid thermal overloading of a line in the event of the unexpected outage of any other line. SFT constraints appear in the dispatch and pricing optimisation model as linear constraints involving two lines. For example:

 -0.902 × OHK_WRK.1+1.274 × THI_WKM1.1 ≤ 605.79

In this case THI_WKM1.1 is the line being protected from overload and OHK_WRK.1 is the line which may cause overload in THI_WKM1.1 if it has an outage (the contingent line). The general form of the SFT constraint is

Equation 1. \[ A F_{m} + B F_{c} \leq C \]

Where \(F_{m}\) is the flow on the protected line and \(F_{c}\) is the flow on the contingent line. The physical nature of the SFT constraint depends on various characteristics of the line being protected, the thermal environment and the mitigating measures available if an outage occurs. The constraint can be expressed as a function of the loading on the line before an outage occurs (pre-contingent) and the loading after an outage occurs (post-contingent). The higher the line is loaded pre-contingency the greater its expected temperature, giving it less capacity to absorb extra power in the event of a contingency.

The physical constraint on the protected line that is modelled with SFT is shown in the diagram 1. This constraint will depend on the thermal environment

Diagram 1. Physical SFT constraint on a single line

In SPD the constraint above is modelled as a linear constraint which represents a tangent of the physical constraint at the point where the pre-contingent power flow matches the power flow in the solution of SPD. Because the constraint may affect dispatch this is an iterative process, the resulting constraint is shown in diagram 2.

Diagram 2. Physical SFT constraint on a single line

Estimating the constraint curves used by SPD

Up to version 5.2.13 estimates of the constraint curves were based on observing historical constraints (see Estimation From Historical Constraints)

However from version 5.2.13 onwards the thermal characteristics of the circuit are used to calculate the thermal constraint curve. This ensures that previously unconstrained lines may be modeled as effectively as possible. It also requires the conductor type and configuration is entered into the model for each modeled line. The methods used to define and use the circuit's thermal characteristics are described in EMO:Use of line conductor information in SFT

SFT constraint modelling in EMO

Diagram 1. SFT Protection factor trait in EMO

Among the traits shown for a circuit in EMO is the SFT protection factor, SFT protection factor curvature and SFT threshold (shown here under the columns "SFT PF", "SFT PFQ", "SFT Threshold" respectively). The SFT protection factor and curvature will determine the nature of the SFT constraints generated by EMO. The SFT protection factor is one minus the estimated slope of the thermal constraint curve at the point it passes through the point of maximum thermal capacity. For example if the slope at that point is such that 0.05 MW extra capacity is available for every 1 MW the flow is below the maximum thermal capacity then the SFT protection factor will be 1.05. Setting the SFT protection factor to a high number will tend to relax any constraints on that line. The SFT protection factor curvature is the rate at which this slope changes as the the powerflow is reduced (per 100MW). These two factors together with the maximum thermal capacity define a quadratic curve that we will call the 'estimated thermal constraint curve', this should be a close approximation of the physical SFT constraint in Diagram 1.

When making a dispatch with Auto-SFT on EMO will search for lines that may be overloaded by an outage in another line. The effect of an outage at the contingent line (C) on the power flow on the protected line (M) can be estimated as a proportion of the flow on C being transferred to M.

Equation 4. \[F'_{m} = F_{m} + B{F}_{m}\]

Where \(F'_{m}\) is the post-contingent flow on the protected line. To ensure the point \(( F_{m}\), \(F'_{m})\) does not lie outside the estimated thermal constraint curve, a linear constraint is added to the dispatch model as follows

Equation 5. \[AF_{m} + BF_{c} \leq A \underline{C}\]

Where A is equal to the slope of the tangent line to the estimated thermal constraint curve and C is the y-intersect of this line. Once the exposed lines are identified and the related constraints are added to the model the dispatch is reiterated. Eventually all relevant SFT constraints should be found and applied.